Title
F218
II point 2 input value
F219
II point 2 frequency
F240
Start frequency
F241
Run frequency
F243
End frequency
F256
Run sleep detection time
F270
Jump frequency1
F271
Jump frequency 1 band
3
F272
Jump frequency2
F273
Jump frequency 2 band
F274
Jump frequency3
F275
Jump frequency 3 band
F311
Reverse inhibited
F359
PID control1
F360
PID1 feedback input select
9
F361
PID1 filter
F362
PID1 proportional gain
F363
PID1 integral gain
F364
PID1 deviation upper-limit
F365
PID1 deviation lower-limit
F366
PID1 differential gain
F367
PID1 set value upper-limit
F368
PID1 set value lower-limit
F369
PID control start wait time
F370
PID1 output upper-limit
F371
PID1 output lower-limit
3. Parameter list of PID control
Parameter name
0 - 100 (%)
0.0 - 590.0 (Hz)
0.0 - 10.0 (Hz)
0.0 - FH (Hz)
0.0 - 30.0(Hz)
0.0 - 600.0(s)
0.0 - FH (Hz)
0.0 - 30.0(Hz)
0.0 - FH (Hz)
0.0 - 30.0(Hz)
0.0 - FH (Hz)
0.0 - 30.0(Hz)
0 - 4
0: Disabled
1: Process PID control
2: Speed PID control
3: Easy positioning PID control
4: Dancer control
5 - 10: -
11: Minus Process PID control
12 - 14: -
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6 - 15: -
16: Pulse train
17: High resolution pulse train (option)
0.0 - 25.0 (s)
0.01 - 100.0
0.01 - 100.0 (s
LL - UL (Hz)
LL - UL (Hz)
0.00 - 2.55 (s)
0.0 - FH(Hz)
0.0 - F367(Hz)
0 - 2400 (s)
LL - UL (Hz)
LL - UL (Hz)
Adjustment range
-1
)
3-2
E6582112
Default setting
100
50.0/
60.0*1
0.1
0.0
0.1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0
0
0
0.0
0.30
0.20
50.0/
*1
60.0
50.0/
*1
60.0
0.00
50.0/
*1
60.0
0.0
0
50.0/
*1
60.0
0.0
VF-AS3