■ Other functions
1) Duty control by digital output
This function convert the output of external PID (analog amount: %) to PWM., and output it to the digital
output terminal. It can be used for ON-OFF control.
(PID3)
When [A340] is one of the value "1", "2", "11", "12", and [A359] is not "0", the result of external PID is
converted to PWM pulse whose period is set by [A359 (sec)], and output to the digital output terminal
"218/219".
4
4
8
(PID4)
When [A370] is one of the value "1", "2", "11", "12", and [A389] is not "0", the result of external PID is
converted to PWM pulse whose period is set by [A389(sec)], and output to the digital output terminal
9
"220/221".
13
9. External PID control
PID output (%)
170
125
90
Digital output
"218/219"
[A359]
Duty: 50%
(125/250)
PID output (%)
170
125
90
Digital output
"220/221"
[A389]
Duty: 50%
(125/250)
9-4
Time(s)
Duty: 68%
Duty: 36%
(170/250)
(90/250)
Time(s)
Duty: 68%
Duty: 36%
(170/250)
(90/250)
E6582112
VF-AS3