2) Analog input
Refer to chapter 6 for detail of analog input characteristic setting.
Example of set value setting
Input the set value to terminal [RX] by 0 to 10V.
Input the feedback signal of 1 to 2 atm into terminal [II] by 4 to 20mA signal. Convert the input level 4-20mA
by terminal [II] to 0-60Hz.
Example of system
Power supply
Set value
0 to 10Vdc
Feedback value
4 to 20mA
Parameter setting
Feedback value
2 atm
1.5 atm
1 atm
4mA
Pressure
(atm)
1.25
1.5
1.75
Set [F389: PID1 set value select]= "2: Terminal RX".
Convert the input level of terminal [RX] into frequency by parameters [F210] to [F213].
VF-AS3
Inverter
R/L1
S/L2
T/L3
RX
CC
II
Feedback value
(Converted frequency)
60Hz
0Hz
20mA
4mA
20mA
Feedback value
(4 to 20mA)
1
4
8
12
16
2
20
U/T1
M
V/T2
W/T3
Pump
Set value
2 atm
1.5 atm
1 atm
0V
10V
Set value
(0 to 10V)
0
2.5
5.0
7.5
10
4-7
E6582112
Pressure
sensor
P
1 to 2 atm
Set value
(Converted frequency)
60Hz
0Hz
0V
10V
Converted frequency
(Hz)
0
15
30
45
60
4. Setting for PID control