Actual output frequency is, regardless of the converted frequency, the output frequency as a result of PID
control.
Impor-
tant
4
9
3) Preset speed
Example of process value setting
Input the set value to terminal [S1] and [S2] by preset speed 1,2 and 3.
Input the feedback signal of 1 to 2 atm into terminal [II] by 4 to 20mA signal. Convert the input level 4-20mA
by terminal [II] to 0-60Hz.
1.5 atm
4. Setting for PID control
Input the set value to maximum of the feedback value or less.
If the process value is 2 atm=10V (60Hz), the deviation becomes zero when the feedback value
reaches 2 atm=20mA (60Hz). The output frequency is fixed even though actual output becomes
even higher, because the feedback value will not exceed over 20mA (60Hz).
Title
F107
Terminal RX input voltage select
F210
RX point 1 input value
F211
RX point 1 frequency
F212
RX point 2 input value
F213
RX point 2 frequency
F216
II point 1 input value
F217
II point 1 frequency
F218
II point 2 input value
F219
II point 2 frequency
F360
PID1 feedback input select
F389
PID1 set value select
Feedback value
2 atm
60Hz
1 atm
4mA
20mA
Parameter name
Feedback value
(Converted frequency)
0Hz
4mA
20mA
4-8
E6582112
Example of setting
0: 0 to +10V
0(%)
0(Hz)
100(%)
60(Hz)
20(%)
0(Hz)
100(%)
60(Hz)
3: Terminal II
2: Terminal RX
Process value
(Converted frequency)
Preset speed 3: 45Hz (1.75 atm)
Preset speed 2: 30Hz (1.5 atm)
Preset speed 1: 15Hz (1.25 atm)
VF-AS3