9.Device Installation Procedures
IEC Rail Installation (Surface Installation)
JIS-Compliant Dimensions Installation (Front-Surface Installation)
*If the display part protrudes from the plate surface at IEC rail and JIS-compliant form installation,
cut the plate at a point 50 mm or more from door opening/closing support.
Board Installation
Board Installation (Using Board Surface Installation Attachment (EMU4-PAT))
29
Energy Measuring Unit
●Applicable IEC Rail
●Installation
(35mm)
①Pull the IEC rail stopper
of the main unit downward.
仮写真
7.3 or more
③Push
●JIS-Compliant Shape
●Installation
Installation Plate
①Check that the IEC rail stopper
of the main unit is on the upper side.
Hook
Installation Plate
Fitting Spring
③Press the main unit downward to that
the fitting spring is inserted into the
groove on the bottom of the main unit.
●Panel Cutting Dimensions
The panel cutting dimensions are as shown below.
Panel thickness allowable for installation is 1.6 to 4.0 mm.
Main Unit External Shape
●Panel Cutting Dimensions
The panel cutting dimensions are as shown below.
Panel thickness allowable for installation is 1.6 to 4.0 mm.
Main Unit External Shape
●Removal
②Hooks
IEC Rail
②Pull up
④Push the IED rail
stopper upward.
●Removal
②Hook the grooves (three
locations) on the upper
part of the main unit
onto the hooks of the
installation plate.
②Lightly lift the bottom of
①Press down the fitting spring.
the main unit and pull out
in the reverse order of the
installation procedures.
●Installation Procedures
Install the screws (M3 X 10) to the installation plate.
Tightening torque: 0.63 N/m
Installation Screws
Installation Plate
Recommended
Cross-recessed head machine screw with spring
Installation Screws
and plain washers JIS B 1188 M3 x 10, Two screws
●Installation Procedures
Install to the installation plate using the installation screws
(M3 x 10) and install the board surface installation attachment.
Tightening torque: 0.63 N/m
Installation Screws
Board Surface
Installation Attachment
*Tighten the attachment with the screws in an environment with a large amount of vibration.
*The installation screws and attachment fixing screws are packaged with the attachment (sold separately).
①Press against the main unit
using your hand so that it
does not fall, and pull the
IEC rail stopper downward.
Attachment Fixing Screws
Installation Plate