Mitsubishi Electric EcoMonitorLight EMU4-BD1-MB Manual page 33

Energy measuring unit
Hide thumbs Also See for EcoMonitorLight EMU4-BD1-MB:
Table of Contents

Advertisement

Specifications of Measurement Terminals
Specifications of Measurement Terminals
Model Name
External appearance
External dimensions (mm)
Installation method
No. of measurement circuits
Auxiliary power rating
①Single-phase 2-wire, single-phase 3-wire and three-phase 3-wire
Auxiliary power rating
②Common use of single-phase 2-wire, single-phase 3-wire,three-phase
    3-wire and three-phase 4-wire*
Single-phase 2-wire
Single-phase 3-wire
Three-phase
3-wire
Three-phase
Input
4-wire
Dedicated
current sensor
Combined with
5A sensor
Electric energy
Reactive energy
Current
/demanded current
Voltage
Power/demanded power
Reactive power
Apparent power
Power rate
Frequency
Harmonic current
Harmonic voltage
Periodic energy
Pulse count value
Operating time
CO
conversion value
2
Other
Communication
Input
Output
Display
Logging function
Compliance with foreign
standards
Note: The above table is a simple comparison chart for the EcoMonitor series. Refer to each model catalog and operation manual for detailed information.
EcoMonitorLight
W75×H90×D75
IEC rail or board-surface installation
1 circuits
100V-240V AC
110,220V AC
100,200V AC
①110,220V AC
②110,220,440V AC
*
63.5/110V 〜 277/480V AC
50A,100A,250A,400A,600A
Compatible up to max. of 6,000 A
Consumed and regenerated
Current of each phase (1, 2, and 3) and overall
Voltage between each wire (1-2, 2-3, 3-1) and overall
*
*
*
*
*
RTU (RS485)
MODBUS
®
CC-Link communication
(*A communication unit is required for CC-Link communication.)
Pulse input/Contact input x 1*
Power use pulse output/*
Alarm output x 1
Main unit LCD screen
Enabled by combination with
logging unit (option)
UL, CE and South Korea Radio Wave Act
* UL regulations compliance is scheduled to be acquired.
EcoMonitorPro
W186×H90×D97(7-Circuit Model)
IEC rail installation
Models with single-phase 2-wire, single-phase 3-wire
and three-phase 3-wire: 1, 3, 5, and 7 circuits
Three-phase 4-wire model: 2 and 4 circuits
100V-220V AC
Common use of single-phase 2-wire,
single-phase 3-wire and three-phase 3-wire
Dedicated three-phase 4-wire*
110,220V AC
100,200V AC
110,220V AC
63.5/110V,110/190V,120/208V,
220/380V,240/415V AC
50A,100A,250A,
400A,600A
Compatible up to max. of 3,000 A
Consumed
  
*
Current of each phase (1, 2, and 3) and overall
Voltage between each wire (1-2, 2-3, 3-1) and overall*
*
*
*
*
*
*
Simple demand (30 min.)
CC-Link communication
Display unit sold separately
Enabled by combination with
logging display unit (option)
*Depending on the model, phase wires and settings.