Huawei SUN2000-50KTL-ZHM3 User Manual page 64

Hide thumbs Also See for SUN2000-50KTL-ZHM3:
Table of Contents

Advertisement

SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
Figure 7-5 Grid-tied point control
Table 7-1 Grid-tied point control
Parameter
Active
Unlimite
power
d
Grid
connecti
on with
zero
power
Issue 03 (2022-08-30)
Description
-
If this parameter is set to Unlimited, the output power of
the SUN2000 is not limited and the SUN2000 can connect
to the power grid at the rated power.
Closed-loop
● If multiple SUN2000s are cascaded, set this parameter
controller
● If there is only one SUN2000, set this parameter to
Limitation
● Total power indicates export limitation of the total
mode
● Single-phase power indicates export limitation of the
Power
Specifies the shortest interval for a single export limitation
adjustment
adjustment.
period
Maximum
Specifies the time for detecting power meter data. If the
protection time
Dongle does not detect any power meter data within the
preset time, the Dongle delivers the preset value of Active
power output limit for fail-safe for protection.
Power raising
Specifies the step for grid-tied power adjustment.
threshold
Active power
Specifies the derating value of the SUN2000 active power
output limit for
by percentage. If the Smart Dongle does not detect any
fail-safe
meter data or the communication between the Smart
Dongle and the SUN2000 is disconnected, the Smart
Dongle delivers the derating value of the SUN2000 active
power by percentage.
Copyright © Huawei Technologies Co., Ltd.
to SDongle/SmartLogger.
Inverter.
power at the grid-tied point. (When a single-phase
meter is connected, only Total power can be selected.)
power in each phase at the grid-tied point.
7 Man-Machine Interaction
57