Parameter
Shutdo
Shutdown at high feed-in
wn at
power
high
feed-in
1
power
Upper feed-in power
threshold for inverter
shutdown (kW)
High feed-in power
duration threshold for
triggering inverter
shutdown (s)
Note 1: This parameter is supported only for the AS4777 grid code.
----End

7.3.2 Apparent Power Control on the Inverter Output Side

On the home screen, tap Settings > Power adjustment to set inverter
parameters.
Issue 03 (2022-08-30)
Description
Communicatio
Specifies the time for determining the communication
n
disconnection between the inverter and the Smart Dongle.
disconnection
This parameter is displayed when Communication
detection time
disconnection fail-safe is set to Enable.
● The default value is Disable.
● If this parameter is set to Enable, the inverter shuts
The default value is 0. This parameter specifies the power
threshold of the grid-connection point for triggering
inverter shutdown.
The default value is 20. This parameter specifies the
duration threshold of high feed-in power for triggering
inverter shutdown.
● When High feed-in power duration threshold for
● When High feed-in power duration threshold for
Copyright © Huawei Technologies Co., Ltd.
down for protection when the grid-connection point
power exceeds the threshold and remains in this
condition for the specified time threshold.
triggering inverter shutdown is set to 5. Shutdown at
high feed-in power takes precedence.
triggering inverter shutdown is set to 20, Grid
connection with limited power takes precedence
(when Active power control is set to Grid connection
with limited power).
7 Man-Machine Interaction