3.3 Smart line module booksize internal air cooling
3.3.2

Safety information

Warning
After disconnecting all the supply voltages, a hazardous voltage will be present in all
components for another 5 minutes. The protective cover must not be opened until this time
has elapsed.
The DC link protective cover must be released using an insulated screwdriver.
Caution
The DC link discharge time hazard warning must be affixed to the modules in the local
language.
A set of labels in 12 languages is available using order number: 6SL3166-3AB00-0AAx.
Notice
The 80 mm clearances above and below the components must be observed.
Caution
The tightening torque of the DC link busbar screws (1.8 Nm) must be checked before
startup.
Danger
In a supply system without regenerative feedback capability (e.g. diesel generator), the
regenerative feedback capability of the smart line module must be deactivated by means of
a jumper between terminals X22.3 and X22.4. The braking energy must then be dissipated
via an additional braking module with a braking resistor in the drive line-up.
Caution
The total length of the power cables (motor supply cables and DC link cables) must not
exceed 350 m in sinusoidal current mode.
3-18
Equipment Manual, (GH2), 04.2004 Edition, 6SL3097-2AC00-0BP0