UNIT CONTROLLER (PC-ARFH1E)

8.8.2.3 Water settings configuration

This menu is only visible for a room thermostat if the controller is not controlling the unit.
Select the desired area to apply the water settings configuration:

Space Heating or Space Cooling water settings
Fixed temperature:
Selection of the temperature for
Circuit 1 or Circuit 2 (heating or
cooling mode).
• Only when water calculation mode
is Fix.
• Circuit 1 or Circuit 2 must be ON to
configure this setting.
Curve:
Selection of the gradient curve for Circuit
1 or Circuit 2 (only for heating mode).
• Only when water calculation mode is
Gradient.
• Range: 0.2 ~ 2.2
• Circuit 1 or Circuit 2 must be ON to
configure this setting.

DHW or Swimming pool water settings
154
PMML0575 rev.2 - 03/2022
Vertex offset:
To modify the curve vertex for Circuit 1 or
Circuit 2 (only for heating mode).
• Only when water calculation mode is
Gradient or Points.
• Range: -10 ~ 10
• Circuit 1 or Circuit 2 must be ON to
configure this setting.
Setting temperature:
Selection of the temperature for DHW or Swimming Pool.
• DHW or Swimming pool must be ON to configure this
setting
• Range:
-
DHW: 30 ºC ~Max. setting temperature
-
Swimming pool: 24 ~33 ºC