YUTAKI CASCADE CONTROLLER ATW-YCC-03
11.13.3.2 Water settings configuration
This menu is only visible for a room thermostat if the controller is not controlling the unit.
Select the desired area to apply the water settings configuration:
Space Heating or Space Cooling water settings
∆θ (Vertex offset):
To modify the curve vertex for Circuit 1 or
Circuit 2 (only for heating mode).
•
Only when water calculation mode is
Gradient or Points (setting in Main device).
•
Range: -10 ~ 10
•
Circuit 1 or Circuit 2 must be ON to
configure this setting.
Fixed temperature:
Selection of the temperature for Circuit 1 or Circuit
2 (heating or cooling mode).
•
Only when water calculation mode is Fix
(setting in Main device).
•
Circuit 1 or Circuit 2 must be ON to configure
this setting.
Hot Water Tank or Swimming pool water settings
292
PMML0575 rev.2 - 03/2022
Setting temperature:
Selection of the temperature for DHW or Swimming Pool.
•
Hot water tank or Swimming pool must be ON to configure
this setting.
•
Range:
DHW: 30ºC ~ Max. setting temperature
-
-
Swimming pool: 24 ~33ºC
Curve:
Selection of the gradient curve for Circuit 1 or
Circuit 2 (only for heating mode).
•
Only when water calculation mode is
Gradient (setting in Main device).
•
Range: 0.2 ~ 2.2
•
Circuit 1 or Circuit 2 must be ON to
configure this setting.