Heat Pump Configuration - Hitachi YUTAKI RWM-2R1E Installation & Operation Manual

Hide thumbs Also See for YUTAKI RWM-2R1E:
Table of Contents

Advertisement

UNIT CONTROLLER (PC-ARFH1E)

8.8.2.8 Heat Pump configuration

Water pump configuration:
Configure the water pump of the
heat pump.
See detailed information in the
next page.
Night shift:
Reduces compressor load in order
to reduce environmental noise,
preferably at night.
See detailed information in the next
page.
162
PMML0575 rev.2 - 03/2022
1 / 2
2 / 2
Outdoor average temperature:
OTC average is used to neutralise the effect of
occasional temperature variations.
The average value of outdoor temperature sampled
over a selected period (between 1 and 24 hours) is
used for the calculation of weather-dependent set point
temperature.
Minimum ON time: In order to reduce a possible
compressor damage, demand ON cycles can be
reduced by determining the time that must pass before
accepting new Demand OFF.
Minimum OFF time: In order to reduce a possible
compressor damage, demand OFF cycles can be
reduced by determining the time that must pass before
accepting new Demand ON.
Seizure protection: The pump seizure protection
function prevents sticking of components due
to long periods of inactivity, by running the
components during a short period every week.
Mixing valves and pumps are fully opened and
then fully closed (time depends on Mixing valve
Run Time Factor).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents