Panasonic Electric Works Nordic AB
MEW01228 Rev: 1
5.3.2.1.1
Operating Instructions Web512 V2.6.x for Web-server II 1598
(Type Fire alarm selected.)
Receiver(s): Up to four e-mail receivers can be written, separated by
a comma (,) or a semicolon (;).
Subject: An e-mail "Subject" text shall be written, e.g. "Fire alarm".
The "Subject" text will be shown in the receivers e-mail Inbox list
view, together with the name of the e-mail sender, date and size.
Body: An e-mail "Body" text shall be written. Up to 500 characters
can be used, including some parameters (see below). In the receiver's
e-mail, the parameters will be replaced with the information they
represent.
NOTE!
In the Test mode e-mail form the "Body" text will
automatically be the list created during the tests, i.e. the "Body" field
is not shown in the e-mail form. In the Web log e-mail form the
"Body" text will automatically be created when there are 100 events in
the log and the e-mail will be sent.
Fire alarm
Fire alarm (incl. Alert Annunciation alarms) e-mail.
Receiver(s), Subject and Body text shall be typed.
The following parameters can be used in the "Body" text:
{1}
The custom text string that contains data about the system,
according to chapter "Text", page 45.
{2}
The alarm point's presentation number, i.e. ZONE–ADDRESS
(e.g. 001-01).
{3}
The user definable text message (alarm text), shown in the fire
alarm system, for the alarm point respectively.
{6}
The actual EBL512 c.i.e. number, i.e. the c.i.e. to which the
alarm point is connected (00-29).
{8}
Date & time, i.e. MM-DD
minute : second), e.g. 11-24 12:34:56
hh:mm:ss (month-day hour :
47