Connecting

5.4 Connecting acoustic emission sensors

5.4
Connecting acoustic emission sensors
Procedure
The procedure for connecting the acoustic emission sensors is as follows:
1. Select the corresponding cable gland:
2. Completely loosen one screw on the mounting plate (Torx T10).
3. Use this screw to attach the cable lug for the shielding connection.
4. Connect the four lines to a four-way block, "Sens1" to "Sens4".
Cable color
Yellow
Green
Brown
Black
5.5

Connecting digital outputs

Procedure
For up to six digital outputs, it is recommended that you use a 12-wire cable, which is fed
through a cable gland ➀.
See also
Cable gland (Page 29)
Terminal assignment (Page 28)
30
Sensor 1 and 3 through cable gland ⑥
Sensor 2 and 4 through cable gland ⑤
Observe the color scheme.
Terminal symbol
yl
gr
br
bl
Sensor 1
Sensor 2
15
25
16
26
17
27
18
28
SITRANS DA400 for oscillating positive displacement pumps
Operating Instructions, 09/2008, A5E00841120-03
Sensor 3
Sensor 4
35
45
36
46
37
47
38
48