QUICK START GUIDE
Infinity S (NE-S) –48V/+24V Aluminum Bus
System
Primary /Secondary
23"
Voltage
wide
Cable crimpers
Torque wrench (0-240 in-lb / 28 Nm)
Screw Drivers - ( Flat # 1 & # 2 Phillips )
Step 1 - Mount the System
Mount the system with a minimum gap of 3 inches behind the system to allow proper airflow.
1. Remove non-conductive coating from mounting rails of frame and apply antioxidant If separate chassis ground is not
provided
2. Attach the system to the frame using a minimum of twelve (six on each side) 12-24 screws (provided).
Torque to 35 in-lb (7.3 Nm) - 5/16" socket.
Page 1
© 2021 ABB. All rights reserved.
NES4824-23-AC5H-PS12-DC52A_M-LVBD-LVLD
AC input
# of Power
AC5H = Terminal
Slots
Strip per Rectifier
# of Distribution
Positions
Socket - 5/16," 7/16" and 1/2", and 9/16"
Wire cutters and strippers
LVBD LVLD
Modbus RTU
options
Interface

Advertisement

loading

Summary of Contents for ABB Infinity S

  • Page 1 QUICK START GUIDE Infinity S (NE-S) –48V/+24V Aluminum Bus System NES4824-23-AC5H-PS12-DC52A_M-LVBD-LVLD LVBD LVLD AC input # of Distribution Modbus RTU Primary /Secondary # of Power options 23” AC5H = Terminal Positions Interface Voltage Slots wide Strip per Rectifier • •...
  • Page 2 Knockout: 3/4” conduit or cord grip - each side Wire: 10 AWG max. Strip: 0.35” (9 mm) Torque: 6 in-lb (7 Nm) Breakers: see Information: Rectifier and Converter Options Page 2 © 2021 ABB. All rights reserved.
  • Page 3 (Panel B) +24V load output and –48V load output. +24V positions 1-13 (left) are noncritical disconnected by the LVLD when operated. Breakers up to 250A are available. Turn breakers OFF before inserting. Page 3 © 2021 ABB. All rights reserved.
  • Page 4 Panel A (upper panel) Upper Breaker position for battery -48V Battery Breakers have Yellow Handle Lower Breaker position for -48V load Breaker Position Colors Blue -48V Load Orange +24V load Yellow -48V Battery Page 4 © 2021 ABB. All rights reserved.
  • Page 5 Multi-pole adapter kits are required for each multi-pole breaker - figure below. Return Bus Adapters Load Return Face lug studs to the Connections rear. (Bus behind Load Connections) Load Connections CC848756916 Page 5 © 2021 ABB. All rights reserved.
  • Page 6: Step 6 - Controller Connections

    Connect and configure Modbus RTU Interface per Pulsar Plus Modbus RTU Interface Quick Start Guide. 1-Wire Battery Temp and Voltage Monitor - Optional J2 1-Wire Data See Information: Battery Monitoring Connections. Step 7 - Install Rectifiers and Converters closed to fully seat the converter. Verify the Page 6 © 2021 ABB. All rights reserved.
  • Page 7: Step 9 - Configure Controller

    Controller Display - Menu > Configuration > System Settings and Menu > Configuration > Batteries. Web pages or EasyView2 - Installation Tab for Date, Time. Site ID and Site Description. Settings Tab > Battery Management for Battery Type and number of battery strings installed. Page 7 © 2021 ABB. All rights reserved.
  • Page 8 Voltage Menu Test Jacks Navigation Front Display Front Display Menu Map Information: Controller Default Voltage Settings and Ranges Parameter Range Valve-Reg Default Flooded NiCd -48V +24V -48V +24V -48V +24V -48V +24V Page 8 © 2021 ABB. All rights reserved.
  • Page 9 848719803 C 5’ thermal probe to thermal probe wireset CC848822321 C 10’ thermal probe to thermal probe wireset 850037334 C 20’ thermal probe to thermal probe wireset Battery Temperature and Voltage Measurement Page 9 © 2021 ABB. All rights reserved.
  • Page 10 5 For the location of the controller alarm jumpers. Connector J4 provides access to the primary customer alarm outputs. J4 is a 20-pin latching connector. Standard Controller Alarm Output Defaults Color Option 1 Color Option 2 Power Critical BL/BK O/BK G/BK W/BK BK/W BL/W BL/R BK/R R/BK Page 10 © 2021 ABB. All rights reserved.
  • Page 11 Standard Controller Alarm Input Defaults J3 Pin Color Alarm Output Cables Alarm Input Cables CC848890137 5 ft. CC848890153 5 ft. Information: Rectifier and Converter Options Recommended Output DC Rectifier Input Voltage Current Eco Rectifier Page 11 © 2021 ABB. All rights reserved.
  • Page 12 Voltage Current NE075DC24A 54A max +24V Orange • Specifications and ordering information are in the Infinity S Ordering Guide available at abbpowerconversion.com • External Surge Protective Device (SPD) is required on all AC inputs. • Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;...
  • Page 13: Safety Statements

    Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network. Page 13 © 2021 ABB. All rights reserved.
  • Page 14 Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as pacemakers. Effects decrease with distance. Page 14 © 2021 ABB. All rights reserved.
  • Page 15 QUICK START GUIDE Notes Page 15 © 2021 ABB. All rights reserved.
  • Page 16 With regard to and illustrations contained therein. Any reproduction, disclosure purchase orders, the agreed particulars shall prevail. ABB AG does to third parties or utilization of its contents–in whole or in not accept any responsibility whatsoever for potential errors or parts –...