Huawei 01075345 User Manual page 75

Hide thumbs Also See for 01075345:
Table of Contents

Advertisement

SUN2000-(2KTL-6KTL)-L1
User Manual
Category
Communication
indicator
Table 6-3 LED indicators 2
Category
Device
replacement
indication
----End
Issue 10 (2023-02-13)
Status
Steady red
LED3
Blinking green at short intervals (on for 0.2s and
then off for 0.2s)
Blinking green at long intervals (on for 1s and
then off for 1s)
Off
NO TE
If the off-grid load is overloaded, indicators LED1 and LED2 on the inverter blink orange
slowly. Reduce the off-grid load power and manually clear the alarm or until the inverter is
recovered. The inverter attempts to restart at an interval of 5 minutes. If the inverter fails to
restart for three times, the interval changes to 2 hours. If the inverter is standby in off-grid
mode, check the inverter alarms and rectify the fault.
Status
LED1
LED2
Steady red
Steady red
Copyright © Huawei Technologies Co., Ltd.
Blinking red at short
intervals (on for 0.2s
and then off for 0.2s)
Steady red
LED3
Steady red
6 System Commissioning
Description
There is an AC
environmental alarm,
such as an alarm
indicating Grid
Undervoltage, Grid
Overvoltage, Grid
Overfrequency, or Grid
Underfrequency.
Fault.
Communication is in
progress.
The mobile phone is
connected to the
SUN2000.
There is no
communication.
Description
The SUN2000 hardware
is faulty. The SUN2000
needs to be replaced.
68