SUN2000-(2KTL-6KTL)-L1
User Manual
Parameter
Backup power SOC
for peak shaving
(%)
Start date
End dete
Peak power (kW)

7.2.2 AFCI

Function
If PV modules or cables are not properly connected or damaged, electric arcs may
occur, which may cause fire. Huawei SUN2000s provide unique arc detection in
compliance with UL 1699B-2018 to ensure the safety of users' lives and property.
This function is enabled by default. The SUN2000 automatically detects arc faults.
To disable this function, log in to the FusionSolar App, enter the Device
Commissioning screen, choose Settings > Feature parameters, and disable AFCI.
Clearing Alarms
The AFCI function involves the DC arc fault alarm.
The SUN2000 has the AFCI alarm automatic clearance mechanism. If an alarm is
triggered for less than five times within 24 hours, the SUN2000 automatically
clears the alarm. If the alarm is triggered for five times or more within 24 hours,
the SUN2000 locks for protection. You need to manually clear the alarm on the
SUN2000 so that it can work properly.
You can manually clear the alarm as follows:
Issue 10 (2023-02-13)
NO TE
The AFCI function works only with Huawei optimizers or ordinary PV modules, but does not
support third-party optimizers or intelligent PV modules.
Method 1: FusionSolar App
Log in to the FusionSolar App and choose Me > Device commissioning. On
the Device commissioning screen, connect and log in to the SUN2000 that
Copyright © Huawei Technologies Co., Ltd.
Description
The value of this parameter
affects the peak shaving
capability. A larger value
indicates stronger peak shaving
capability.
● Set the peak power range
based on the start time and
end time. The peak power is
configured based on
electricity prices in different
time segments. You are
advised to set the peak
power to a low value when
the electricity price is high.
● A maximum of 14 time
segments are allowed.
7 Man-Machine Interaction
Range
[0.0, 100.0]
Backup power SOC for
peak shaving > Backup
power SOC (when
BackUp is enabled) >
End-of-discharge SOC
-
[0.000, 1000.000]
83