4.1 Notes on Selecting the Installation Location

1.
Avoid places within the immediate proximity of equipment producing electrical
interference (such as motors, transformers, radio transmitters, electrolytic cells, or
other equipment causing electromagnetic or electrostatic interference).
2.
Avoid places where excessive pipe vibration occurs.
3.
Avoid places where fluid is pumped in a pulsating manner
4.
Avoid places where there is direct sunlight. If this is unavoidable, use an appropriate
shade
5.
Avoid places where corrosive atmospheres or high humidity conditions obtain.
6.
Avoid places where there may be limited access such as pipes installed next to high
ceilings or constricted areas where clearance for installation or maintenance work is not
provided.
7.
Design piping so that the detector pipe is always filled with fluid, whether the fluid is
flowing or not.
8.
The detector has no adjustable piping mechanism. Install an adjustable short pipe where
needed.
9.
Chemical injections should be conducted on the downstream side of the flowmeter.
10. The maximum length of the cable that connects the detector and converter is 300m.
Select the converter installation location so that the distance between the detector and
converter dose not exceed 300m.
 