Hitachi PC-ARFG2-M Installation & Maintenance Manual page 22

Advanced color wired remote controller
Hide thumbs Also See for PC-ARFG2-M:
Table of Contents

Advertisement

6. Function Selection
No.
Item
Optional Function
Setback Activating Temp. for Heat
147
rE
Mode
Setback Activating Temp. for Cool
148
rF
Mode
S1
Econo outside air high humidity
149
(*15 )
control
150
S2
24-hour ventilation control
151
S3
NightPurge control
152
S4
Fan control based on CO2 sensor
Rapid ventilation control at the
153
S5
start of operation
154
S6
Humidifier drying operation
155
S7
Suction humidity level setting
156
S8
Suction humidity control setting
(*1):
Even if temperature sensor selection is changed through "P3" setting, the compensation value will not be changed automatically. Please
change b1 setting according to temperature sensor selection.
(*2):
The default temperature compensation is +2°C for Floor Exposed type & Floor Concealed type.
(*3):
The "02", "03", "04" settings may not be available depending on the type of indoor unit. When connecting multiple indoor units, do separate
settings.
(*4):
Standard type.
(*5):
It is not applicable for Auto mode.
(*6):
If Duct type models, 00: Increasing fan speed 1 (standard), 01: Increasing fan speed 2 (high static pressure), 02: Standard (low static
pressure).
(*7):
Since it depends on the model, please refer to the Service Manual of each model.
(*8):
If the set temperature is changed and kept within the set time at "F4", the temperature is automatically changed to "F5" and "F6". (If the set
temperature is out of range at "F5" and "F6", it is applied within the upper and lower limits for the set temperature.)
(*9):
Applicable to the fan, cooling and dry operation modes.
(*10): Applicable to the heating operation mode.
(*11): When the unit is restarted by the controller, the temperature automatically changes to the setting temperature of "F5" or "F6".
(*12): Available only for 4-Way Cassette Type, 4-Way Cassette Compact Type, 2-Way Cassette Type, 1-Way Cassette Type, Ceiling Type.
(*13): Setting "P4" to "01", then the temperature of selected thermistor (sensor) can be shown.
(*14): Setting "01" can show sensor temperature selected in "P3".
(*15): Items "S1~S8" are available only for new econo-fresh units.
19
Individual
Setting
Setting
Condition
00
15.0°C (59°F)
01
16.0°C (60°F)
02
17.0°C (62°F)
03
18.0°C (64°F)
04
19.0°C (66°F)
×
05
10.0°C (50°F)
06
11.0°C (52°F)
07
12.0°C (54°F)
08
13.0°C (56°F)
09
14.0°C (58°F)
00
26.0°C (78°F)
27.0°C (80°F)
01
28.0°C (82°F)
02
29.0°C (84°F)
03
30.0°C (86°F)
04
×
31.0°C (88°F)
05
06
32.0°C (90°F)
07
33.0°C (92°F)
08
34.0°C (94°F)
09
35.0°C (95°F)
10
25.0°C (77°F)
00
Unavailable
-
01
Available
00
Unavailable
-
01
Available
Unavailable
00
-
01
Available
00
Unavailable
-
01
Available
00
Unavailable
-
01
Available
00
90 min
-
01
180 min
02
Unavailable
00
Unavailable
01
High
-
02
Med
03
Low
00
Standard
-
01
High Humidity
02
Low Humidity
Contents
A16381TMEL