Chapter 6 Specifications; Inverter Rating - Mitsubishi Electric FR-A802-E Instruction Manual

Separated converter type
Table of Contents

Advertisement

6
SPECIFICATIONS
This chapter explains the specifications of this product.
Always read the instructions before use.
6.1

Inverter rating

 400 V class
• Inverter
Model FR-A842-[]
Applicable motor
*1
capacity (kW)
Rated capacity
*2
(kVA)
Rated current (A)
Overload current
*3
rating
*4
Rated voltage
Regenerative
braking
*5
torque
(when used
with the converter
unit (FR-CC2))
Power supply voltage
Control power supply auxiliary input
Permissible control power supply auxiliary
input fluctuation
Protection rating of structure (IEC 60529)
Cooling system
Approx. mass (kg)
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.
*2
The rated output capacity is the value with respect to 440 V output voltage.
*3
The percentage of the overload current rating is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow
time for the inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about
*5
Value for the ND rating
*6
FR-DU08: IP40 (except for the PU connector)
*7
For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection. (For details, refer to the FR-A800 Instruction Manual
(Detailed).)
118
6. SPECIFICATIONS
6.1 Inverter rating
07700
315K
SLD
400
LD
355
ND (initial setting)
315
HD
280
SLD
587
LD
521
ND (initial setting)
465
HD
417
SLD
770
LD
683
ND (initial setting)
610
HD
547
SLD
110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature of 40°C
LD
120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
ND (initial setting)
150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
HD
200% 60 s, 250% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
Three-phase 380 to 500 V
Maximum brake
10% torque, continuous
torque
430 to 780 VDC
Single-phase 380 to 500 V, 50/60 Hz
Frequency ±5%, voltage ±10%
*6
Open type (IP00)
Forced air
163
08660
09620
355K
400K
450
500
400
450
355
400
315
355
660
733
587
660
521
587
465
521
866
962
770
866
683
770
610
683
*7
163
243
10940
12120
450K
500K
560
630
500
560
450
500
400
450
834
924
733
834
660
733
587
660
1094
1212
962
1094
866
962
770
866
243
243
.

Advertisement

Table of Contents
loading

Table of Contents