Performance Ratings Pm230; Table 6- 1 Performance Ratings - Siemens SINAMICS G120P Hardware Installation Manual

Power module pm230 ip55/ul type 12
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

Technical specifications

6.1 Performance ratings PM230

Definitions
 LO input current
 LO output current 100 % of the permissible output current with a load cycle according to
 LO power
 HO input current
 HO output current 100 % of the permissible output current with a load cycle according to
 HO power
6.1
Performance ratings PM230
Common performance ratings of the Power Module
Table 6- 1
Feature
Line operating voltage
Input frequency
Power factor λ
Overload capability for
low overload (LO)
Overload capability for
high overload (HO)
Inrush current
Pulse frequency
Electromagnetic
compatibility
Protection level
Operating temperature range
Storage temperature
Humidity
72
100 % of the permissible input current with a load cycle according to
Low Overload.
Low Overload.
Power of the Unit at LO output current.
100 % of the permissible input current with a load cycle according to
High Overload.
High Overload.
Power of the Unit at HO output current.
Performance ratings
Specification
3 AC 380 V ... 480 V ± 10%
The permissible voltage depends on the operational altitude
47 Hz ... 63 Hz
0.9
1.1 x LO output current (110%) for 57 s every 300 s
1.5 x LO output current (150%) for 3 s every 300 s
1.5 x HO output current (150%) for 57 s every 300 s
2.0 x HO output current (200%) for 3 s every 300 s
Less than rated input current
4 kHz factory setting, can be increased in 2 kHz steps up to 16 kHz.
Increasing the pulse frequencies leads to an output current reduction.
Category C1 and C2 in accordance to IEC61800-3 as detailed in the
section "Motor cable lengths and cross-sections".
IP55 - UL Type 12.
Note: With a blanking plate, the appropriate gland plates, cable glands
and grommets must be fitted to achieve the IP55 (UL Type 12) level of
protection. If an IOP is fitted the protection rating of the Power Module
becomes IP54/UL Type 12.
without derating
0 °C ... +40 °C (32 °F ... 104 °F)
with derating
up to 60° C (140° F)
-40 °C ... +70 °C (-40 °F ... 158 °F)
< 95% RH - non-condensing
Hardware Installation Manual, 2010-07-02, A5E02923635A AB
Power Module PM230 IP55

Advertisement

Table of Contents
loading

Table of Contents