Appendix
A.3 EMC overall performance
Note
To achieve this performance the default switching frequency should not be exceeded. The
PM230 complies with the above mentioned EMC emission requirements, only at the default
settings of the Power Module.
The limits will not be met if the drive is not installed in accordance with good EMC practices.
Harmonic Currents
The harmonic current emissions from the SINAMICS PM230 is as follows:
Table A- 3
Rating
FSA ... FSF
(400 V, 370 W ... 90.0 kW)
Note
Units installed within the category C2 (domestic) environment require connection to the
public low-voltage power supply network. Please contact your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.
EMC Immunity
The SINAMICS PM230 has been tested in accordance with the immunity requirements of
category C3 (industrial) environment:
Table A- 4
EMC Phenomenon
Electrostatic Discharge (ESD)
Radio-frequency
Electromagnetic Field
Amplitude modulated
Fast Transient Bursts
Surge Voltage
1.2/50 μs
Conducted
Radio-frequency Common Mode
84
Harmonic Currents
Typical Harmonic Current (% of rated input current)
5th
20
EMC Immunity
Standard
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
7th
11th
13th
14
9.1
7.7
Level
4 kV Contact discharge
8 kV Air discharge
80 MHz ... 1000 MHz
10 V/m
80% AM at 1 kHz
2 kV @ 5 kHz
1 kV differential (L-L)
2 kV common (L-E)
0.15 MHz ... 80 MHz
10 V/rms
80% AM at 1 kHz
Hardware Installation Manual, 2010-07-02, A5E02923635A AB
17th
19th
23rd
5.9
5.3
4.3
Performance
Criterion
A
A
A
A
A
Power Module PM230 IP55
25th
4.0