6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION

4. MOUNTING

The connection box must be mounted in the ceiling. Screws are not supplied.
(Measure in mm)
a) Cut out the required number of knockouts and apply the compression glands. Tighten the compression glands firmly.
b) Mount the connection box in the ceiling.
c) Insert the cables in the compression glands.
If the outer cable diameter is < 6 mm, insert the enclosed rubber tube before installation of the cable. If the
outer cable diameter is ≥ 6 mm, do not use the enclosed rubber tube.
d) Tighten all compression glands with 4 Nm or more.
e) Connect the wires from the CIE to the A and B push-on connectors.
f) Connect the next unit or the end-of-line device to the other pair of A and B push-on connectors.
g) Mount the detector on the connection box with the two enclosed screws. Tighten the screws firmly with 1.4 Nm or more.