7. TECHNICAL DATA 6295

All current consumptions are valid by nominal voltage and by 25 °C.
Voltage:
Allowed
Normal
Current:
Quiescent
Active
Current limitation required when active
Alarm resistance
Internal capacitance
Internal inductance
Short circuit isolator
Internal battery
Material
Ambient temperature:
Operating
Storage
Static response temperature
Ambient humidity
Ingress protection rating
ATEX classification
Size:
Ø x H
Weight:
Colour
12 – 30 V DC
24V DC (Zone line voltage)
0 mA
35 mA
Must be minimum 6 and maximum 40 mA
400 Ω
3 nF
0 nF
No
No
FR ABS and polycarbonate
-40 to +50 °C
-45 to +70 °C
57 °C
Maximum 95 % RH (Non condensing)
IP67
II 3 G Ex ic IIC T5 Gc X, II 3 D Ex ic IIIC T100°C Dc X
-40°C ≤ Ta ≤ 50°C / EN IEC 60079-0:2018,
EN 60079-11:2012
100 x 75 mm
82 g
Grey (N8, Munsell colour code)