Tested for
Vibrations
Shock
Climatic ambient conditions
The following table shows the climatic ambient conditions for operation of the device.
Ambient conditions
Temperature for IFP1200 /
IFP1500 / IFP 1900 Basic:
Temperature for IFP2200
Basic:
Temperature for IFP1200
Basic C:
Relative humidity
Atmospheric pressure,
operation elevation
Multiplication factors for equipment ambient temperature of operation at altitudes up to 3000m,
tested in accordance with IEC 61131-2:2017
Altitude
0 to 2000 m
3000 m
: Equipment ambient temperature rating at 2000 m.
1
IFP Basic
Operating Instructions, 06/2023, A5E46178354 - AD
Test standard
Vibration test in accordance
with IEC 60068, part 2-6 (si-
nusoidal)
Shock test in accordance with
IEC 60068, Part 2-27
Permitted range
horizontal mounting
0 to 45 °C
Vertical mounting
0 to 45 °C
horizontal mounting
0 to 40 °C
Vertical mounting
0 to 40 °C
horizontal mounting
0 to 60 °C
Vertical mounting
0 to 50 °C
10 to 85% at 30 °C, no condensation
1140 to 700 hPa
2
7.5 Technical specifications
Comments
Type of vibration:
Frequency cycles at a rate of change of
1octave/minute.
10 to 500 Hz, constant acceleration 3g
Vibration duration:
10 frequency cycles per axis in each of the three mu-
tually vertical axes
Type of shock: Half-sine
Severity of shock:
Peak value 15 g, duration 11 ms
Direction of shock:
3000 shocks in ± direction of axis in each of the three
axes vertical to each other
Comments
Tilt angle max.
45°
Tilt angle max.
45°
Tilt angle max.
45°
Corresponds to an elevation
of -1000 to 3000 m
Derating ratio for temperature
1.0
0.9
Technical information
Note:
Tilt angle is
only supported
for the horizon-
tal mounting.