3.7

Battery Disposal

For any questions regarding disposal please contact Toshiba Customer Support Center (855) 803-7087.
3.8

Defective Battery Handling

For shipping (returning) Damaged / Defective / Recalled SCiB Lithium Batteries (Modules), the following requirements are
to be followed:
● Contact Toshiba International Corporation UPS Service for RMA#.
● SCiB Modules being returned must be packaged to meet shipping regulations outlined in UN 3480, 49 CFR
173.185 (f).
This is for lithium batteries that have been damaged or identified by the manufacturer as being defective for
safety reasons and may be transported by highway, rail, or vessel.
● Place the SCiB module in non-metallic inner packaging that completely encloses the battery.
Inner packaging is surrounded by cushioning material that is non-combustible, non-conductive, and absor-
bent. It should prevent:
■ Short circuits.
■ Movement within the package.
e.g. non-conductive plastic bag, non-conductive bubble wrap, non-conductive packaging cushion paper
● Each SCiB Module properly inner packaged is individually placed in a UN specification package meeting Pack-
ing Group I performance level (metal, wooden, or solid plastic box) (This means if shipping multiple SCiB mod-
ules, each one has to be individually wrapped before being placed in an appropriate shipping container (wood,
or solid plastic box).
● Returned SCiB module must ship by highway, rail, or vessel. Air shipment is forbidden.
● Returned SCiB module must be marked with the Lithium Battery mark
● Returned SCiB module must also be marked with an indication the package contains "damaged / defective
lithium-ion / lithium-metal battery"
Characters are to be at least 12 mm (0.47in.) high.
● Returned SCiB module must be marked with the Toshiba International Corporation UPS RMA#.
If possible the Returned SCiB module should be shipped at 30% SOC
288V SCiB Energy Storage System Installation and Operation Manual – 203810-000
CAUTION
Do not dispose of lithium ion batteries via incineration.
Lithium battery disposal shall be in compliance with the local and/or
regional hazardous waste disposal regulations for your area
Other nations and some US states may differ in the requirements for dis-
posing of hazardous waste. Contact your state and/or local environmen-
tal agency for specifics on disposing of hazardous waste in your area.
Steps shall be taken to prevent the short circuit of disposed batter-
ies by insulating the terminals (e.g. insulating tape) (Ref. Section 13,
MSDS SB-SDS-P5001E dated 4/08/2016)