WARNING!
Ensure that mains fault current is compatible with proper operation of the protection devices
incorporated in the equipment (5 kA rated interrupting capacity).
Power specifications, model M2K85B and M2K86B (Regulatory Model Number: VCVRA-1804-01)
Dedicated line
Number of power wires
Input voltage
Input frequency
Maximum power consumption
Maximum load current
Branch circuit breaker (required)
Copper wire, minimum cross-sectional area
Power wire terminals
Protective Earth (PE) terminal
Power wires can be L1 & L2 or L & N, depending on the country.
1
This product has been evaluated to ±10% of the rated nominal voltage range (200–240 V) to allow for line fluctuation.
2
If the wire is more than 4.5 m (15 ft) long, HP recommends increasing the wire gauge appropriately.
3
WARNING!
Ensure that mains fault current is compatible with proper operation of the protection devices
incorporated in the equipment (5 kA rated interrupting capacity).
Example of a single-circuit connection to the building's electrical system
The certified electrician needs to configure the proper wiring based on each specific country and building
installation, ensuring that it meets the voltage, current, and power requirements specified in the above table.
NOTE:
The electrician must determine the appropriate circuit breakers, which are not shown in these schemes.
1.
L1 wire
2.
L2 wire
3.
Protective earth wire
4.
Jumpers (0360-3729 provided)
5.
Circuit breaker
Circuit breaker (required)
The customer-provided circuit breaker must meet the requirements of the printer and should be in accordance
with the Electrical Code requirements of the local jurisdiction where the equipment is installed.
ENWW
Yes
2 + Protective Earth (PE) wire
1
200–240 V
2
50/60 Hz
7200 W
40 A
2 poles, 40 or 50 A (Europe)
2 poles, 50 A (rest of the world)
10 mm² (8 AWG)
3
Straight wire to terminal block
Straight wire with ferrule to ground block
Electrical requirements