Lamp duct recommendation
In order for the printer to function correctly, the lamp exhaust duct should create no more than 125 Pascals of
back-pressure at 3680 liters per minute (0.5 inches of water at 130 ft³/min) of air flow. In order to achieve this
with a passive exhaust duct:
A duct of at least 10 cm (4 in) is required
●
Remove the silencing foam from the duct before connecting any external ducting.
●
Avoid sharp bends in the duct, and use no more than three bends of minimum radius 20 cm (8 in).
●
For a duct longer than 3 m (10 ft), the diameter of the duct should be increased, or use no more than two
bends up to 6 m (20 ft) in radius.
50
Appendix B Ducts and HVAC recommendation
ENWW