Ducts and HVAC recommendation

Energy balance

Air conditioning in the work area should take into account that the equipment produces heat. The temperature of
the air coming out of the printer may be up to 90°C (194°F) at the lamp exhaust duct, at sea level.
Typically, the printer's power dissipation without local exhaust is in the range of 4–6 kW (13.6–20.5 kBTU/h).
If local exhaust is installed for lamp outlet, the power dissipation into the room decreases to 2.5 kW (8.5 kBTU/h).
Cooling to maintain operating temperature may be provided through any combination of HVAC, heat pump, and
other cooling methods.
Printer generates 4–6 kW/h (13.6–20.5 kBTU/h)
48

Appendix B Ducts and HVAC recommendation

Printer air flow