(180-200kgf.cm)
32-39 N.m
(320-390kgf.cm)
49-59 N.m
(490-590kgf.cm)
57-71 N.m
(570-710kgf.cm)
67-101 N.m
(670-1010kgf.cm)
85-110 N.m
(850-1100kgf.cm)
6.After connecting the copper pipes to the indoor
unit,wrap the power cable , signal cable and the
piping together with binding tape.
7.Thread this pipeline through the wall and connect
it to the outdoor unit.
8.Insulate all the piping , including the valves of the
outdoor unit.
9.Fix the water receiver (supplied in Accessories box)
to the indoor unit by a screw.
ST4.8*12 screw
10.Open the stop valves of the outdoor unit to start
the ow of the refrigerant between the indoor and
outdoor unit.
NOTICE
Two ST4.8*12
screws are supplied,
one of which
is spare.