  • Page 1 — O P T I ON S FO R A B B D R I V E S FPTC-01/02 thermistor protection with the PROFIsafe safety functions module FSPS-21 for ACS880 drives Application guide...
  • Page 2: Table Of Contents

    CO NT ENTS — Contents 1. Introduction ..............................3 2. Safety instructions ............................3 3. System overview ............................. 3 3.1. Intentional misuse ..............................4 4. Connection procedure ........................... 4 4.1. Configuration ................................. 5 4.2. Start-up procedure .............................. 6 4.3. Validation ................................6 5.
  • Page 3: Introduction

    FPTC-02 ATEX-certified thermistor protection module Ex II (2) GD (option +L537+Q971) with the FSPS-21 PROFIsafe safety functions module (option +Q986) in ACS880 drives. The presented combination is not available with plus codes. You can order the FPTC-01/02 and FSPS-21 option modules as add-on kits:...
  • Page 4: Intentional Misuse

    If you do, injury or death, or damage to the equipment can occur. Refer to the applicable user’s manuals for information on how to install the safety modules. To connect the FPTC-01/02 and FSPS-21 modules to the ACS880 drive, strictly obey the wiring diagram in Figure 1.
  • Page 5: Configuration

    9. Connect the white wire to FPTC-01/02 XSTO2:21. 10. Add an extra wire between FPTC-01/02 XSTO1:12 and pin 3 on the drive-side STO connector plug. 11. Add an extra wire between FPTC-01/02 XSTO2:22 and pin 4 on the drive-side STO connector plug.
  • Page 6: Start-Up Procedure

    Before you start the system, make sure that the motor temperature is less than the monitored temperature limit and that the FPTC-01/02 module does not activate the STO function (STO circuit is closed). Otherwise, the FSPS-21 module does not start correctly and keeps the STO function active. If this happens, examine the motor, PTC sensor and wiring of the STO circuit, and either start the system again or boot the FSPS-21 module with parameter 51/54.27.
  • Page 7: Related Documents

    FSPS-21 PROFIsafe safety functions module 3AXD50000158638 User’s manual FPTC-02 ATEX-certified thermistor protection module Ex II (2) GD (option +L537+Q971) for ACS880 drives User’s 3AXD50000027782 manual FPTC-01 thermistor protection module (option +536) for 3AXD50000027750 ACS880 drives User’s manual 5.2. Certificates Ref. Document Document number ACS880/ACS880LC TÜV NORD STO certificate...
  • Page 8: Further Information

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 10 Copyright© 2023 ABB. All rights reserved.

This manual is also suitable for:

Fptc-02

Table of Contents