Hitachi RCUE40AG2 Service Manual page 105

Air cooled water chillers, cooling only and heat pump, cooling capacity 106/112 kw - 585/556/1030 kw
Table of Contents

Advertisement

Troubleshooting
Flowchart at abnormal occurrence
Abnormal occurrence in
refrigerant cycle
Could it
NO
be a temporal
phenomenon due to an
accidental factor?
YES
-
Stop the compressor of
correspondent cycle
-
Count retry times
Retry
control by
YES
the same abnormal
reason is performed specifi ed
times within specifi ed
period?
NO
-
Retry code is indicated
-
Compressor is re-started
in 3 min.
(Alarm stop)
-
compressor of correspondent
cycle is stopped
-
indication of alarm code
Abnormal indication of Option / Remote Controller Switch
Indication lamp of remote controller side distinguishes "Run", "Alarm", and "Stop":
-
"Run": Red light indication lamp on.
-
"Alarm": Light red indication lamp on. Light orange indication lamp on: in case of option switch use
-
"Stop": Light red indication lamp off.
pag. 103
SMGB0003 rev.0 - 01/2007
Abnormal occurrence in fan
Is
it judged
that it is possible to
continue operation although fan
is stopped temporally
YES
-
Stop the correspondent fan
-
Count retry times
Retry
control by
the same abnormal
reason is performed specifi ed
times within specifi ed
period?
YES
1
abnormal
NO
fan per 1 cycle?
And are all fan manual set
SW ON?
YES
-
Correspondent fan is stopped
REMOTE OUTPUT (ALARM)
terminals (n54~n55)
-
No indication of alarm code (fan
under stop by abnormal function is
indicated in check mode)
Operation continues
NO
-
Stop the compressor of
correspondent cycle
-
Count retry times
NO
(*) Fan restart by itself
-
no indication of retry code
(fan under retry is indicated
in check mode)
-
correspondent fan is re-
started in 10 sec.
(*) Cycle retry
-
indication of retry code
-
compressor is re-started
in 3 min.
5
5