Control system
Prevention of high pressure excess increase
Discharge pressure
Discharge pressure
Prevention of high pressure excess decrease
Discharge pressure
Discharge pressure
2. Heating operation
Basically unit is operated with Max frequency, but under the following conditions revolution number control is
performed.
Prevention of low pressure excess increase
Fan speed control is activated if "suction pressure
*Released at ambient temperature
pag. 77
SMGB0003 rev.0-01/2007
≥
2.2MPa
out put +10Hz
≥
2.5 MPa
out put max. frequency
≤
0.9 MPa
out put -10Hz
≤
0.8 MPa
out put min. frequency
≥
0.6 MPa" and "ambient temperature
≤
20 °C
≥
25ºC"
4 4