Hitachi RCUE40AG2 Service Manual page 145

Air cooled water chillers, cooling only and heat pump, cooling capacity 106/112 kw - 585/556/1030 kw
Table of Contents

Advertisement

Troubleshooting
Discharge gas
control is activated
(- alarm)~
(- alarm)
Thermal relay for
compressor is
activated
(- alarm)~
(- alarm)
Compressor internal
thermostat is
activated
(- alarm)~
(- alarm)
Fan internal
thermostat is
Unit stops
activated
during
(- alarm)~
cooling
(- alarm)
operation
Pump over-current
relay is activated
( alarm)
Freeze protection
control is activated
( alarm)
pag. 143
SMGB0003 rev.0 - 01/2007
Suction gas
(Air heat exchanger side)
temperature
is excessively
high (excessive
Expansion Valve Clogging
Expansion Valve Clogging
Expansion Valve Clogging
superheat)
Strainer Clogging
Strainer Clogging
Strainer Clogging
Discharge gas
Check thermistor resistance
Thermistor Failure
Thermistor Failure
Fan motor bearing
failure
failure
Single Phase
Single Phase
Check magnetic contactor
Running
Running
Motor Insulation
Measure insulation
Deteriorated
Deteriorated
Power Voltage excessively
Compressor Drive
Power Voltage Phase
Excessive Current
Discharge pressure is
excessively high
excessively high
Power Fuse melted
Power Fuse melted
Loose Power Terminal
Single Phase
Running
Contact point of compressor
Contact point of compressor
Motor magnetic Contactor
Compressor Bearing
Compressor Bearing
Failure
Failure
Compressor Motor
Compressor Motor
Measure insulation
insulation Failure
insulation Failure
Compressor Motor
Compressor Motor
Measure current of
Over-current relay
compressor motor
Failure
Failure
Check freezing of water,
Check freezing of water,
Pump locked
clogging of foreign particle
clogging of foreign particle
Pump Over-current
Pump Over-current
Check the RC value and
relay RC value
pump running current
Wrong
Wrong
Pump Over-current
Pump Over-current
Push reset button. Check
Push reset button. Check
relay Failure
relay Failure
the running current
the running current
Check the difference of
Check the difference of
Shortage of water
temperature between inlet
Flow
and outlet of chilled water
and outlet of chilled water
Water Strainer Clogging
Water Strainer Clogging
Water Strainer Clogging
Pump reverse
Check rotative direction
rotated
rotated
Air mixed
Air mixed
Open Air Vent Valve
Open Air Vent Valve
Open Air Vent Valve
Thermistor Failure
( alarm)
Check inlet temperature of
( alarm)
( alarm)
( (  alarm)
alarm)
Check valve
Check valve
Malfunction
Malfunction
Replace or clean the strainer
Replace or clean the strainer
Replace discharge gas
Lock Status
Replace magnetic switch
resistance
resistance
Set voltage within working
Set voltage within working
high or low
high or low
range during operation
range during operation
Measure the voltage in each
interphase and ask Power
Imbalance
Company for the advice
Company for the advice
Screw
Screw
Replace contact points
Roughness
Roughness
Lock Status
resistance
resistance
Replace over-current Relay
Change the RC value or
replace magnetic contactor
Replace magnetic contactor
Repair to correct direction
chilled water
Replace check valve
Remove Clogging
Remove Clogging
Remove Clogging
thermistor
thermistor
Replace fan motor
Replace fan motor
Analyze the cause
5
5
Replace power fuse
Replace power fuse
Replace power fuse
Retighten the screw
Replace compressor
Remove them
Increase water fl ow
Clean the strainer
Clean the strainer
Clean the strainer
Evacuate Air
Evacuate Air
Replace Thermistor