ABB ACH550-UH-011A-6 User Manual page 421

Table of Contents

Advertisement

X1
10
+24V
11
GND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
1
Digital input impedance 1.5 kohm. Maximum voltage for digital
inputs is 30 V.
2
Default values depend on the macro used. Values specified are for
the default macro. See chapter
Note: Terminals 3, 6, and 9 are at the same potential.
Note: For safety reasons the fault relay signals a "fault" when
the ACH550 is powered down.
416
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Hardware description
Auxiliary voltage output 24 V DC / 250 mA (reference to
GND). Short circuit protected.
Auxiliary voltage output common (connected internally as
floating).
Digital input common. To activate a digital input, there
must be ≥+10 V (or ≤-10 V) between the input and
DCOM. The 24 V may be provided by the ACH550
(X1:10) or by an external 12...24 V source of either
polarity.
Digital input 1, programmable. Default
Digital input 2, programmable. Default
Digital input 3, programmable. Default
speed 1 (parameter 1202).
Digital input 4, programmable. Default
(parameter 1608).
Digital input 5, programmable. Default
Digital input 6, programmable. Default
Relay output 1, programmable
2
Default
= Ready
Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)
Relay output 2, programmable
2
Default
= Running
Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)
Relay output 3, programmable
2
Default
= Fault (-1)
Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)
ACH550-01 User's Manual
2
= start/stop.
2
= not used.
2
= constant
2
= Start enable 1
2
= not used.
2
= not used.
Application macros and
Technical data
wiring.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550-01Ach550

Table of Contents