Ambient conditions
The following table lists the ACH550 environmental
requirements.
Altitude
Ambient temperature
Relative humidity
Contamination levels
(IEC 60721-3-3)
Sinusoidal vibration
(IEC 60068-2-6)
Shock (IEC 68-2-29)
Free fall
440
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Ambient environment requirements
Installation site
0...1000 m (0...3,300 ft)
1000...2000 m
(3,300...6,600 ft) if P
N
I
derated 1% for every
2N
100 m above 1000 m
(300 ft above 3,300 ft)
2000...4000 m
(6,600...13,200 ft):
Contact your local ABB
representative.
No frost allowed
400 V drives:
See the available currents
in -15...50 °C (5...122 °F)
in the table on page
399
200 V drives:
-15...40 °C (5...104 °F),
max. 50 °C (122 °F) if P
and I
derated to 90%
2N
5...95%, no condensation
allowed
No conductive dust allowed
The ACH550 should be
installed in clean air
according to enclosure
classification.
Cooling air must be clean,
free from corrosive
materials and free from
electrically conductive dust.
Chemical gases: Class 3C2
Solid particles: Class 3S2
Mechanical conditions:
Class 3M4 (IEC60721-3-3)
2...9 Hz 3.0 mm (0.12 in)
2
9...200 Hz 10 m/s
2
(33 ft/s
)
Not allowed
Not allowed
ACH550-01 User's Manual
Storage and transportation in the
protective package
and
-40...70 °C (-40...158 °F)
.
N
Storage
No conductive dust allowed
Chemical gases: Class 1C2
Solid particles: Class 1S2
Transportation
No conductive dust allowed
Chemical gases: 2C2
Solid particles: Class 2S2
In accordance with ISTA 1A
and 1B specifications.
2
Max.100 m/s
(330 ft/s
76 cm (30 in), frame size R1
61 cm (24 in), frame size R2
46 cm (18 in), frame size R3
31 cm (12 in), frame size R4
25 cm (10 in), frame size R5
15 cm (6 in), frame size R6
Technical data