Installing the Device
2.5.2 Testing Dielectric Strength
2.
3.
16
1
2
5
Surge Ground Terminal
1
Positive (+) Terminal
2
Chassis Ground Terminal
3
Negative (-) Terminal
4
Jumper
5
Chassis Ground Connection
6
Figure 2.7
Jumper
Connect one terminal from the HIPOT tester to the positive terminal and the
negative terminal. Connect the second terminal of the HIPOT tester to chassis
ground terminal. Do not connect the HIPOT tester to surge ground terminal.
Following the test, install the metal jumper between the surge ground terminal
and the chassis ground terminal.