5. Energy Management

5-1. Energy Use Status

On the Energy Use Status screen, the energy-control-related status, such as electric energy consumption,
operation time, and outdoor temperature, can be displayed in a graph. Operators can check the detailed status
of given indoor units by specifying the date to display the data per group, block, or unit address. Also, the status
of other indoor units can be displayed at the same time for comparison.
Displaying energy-control-related status of each hour, day, and month in a graph visualizes the energy-saving
status.
Click [Energy Management] in the menu bar, and then click [Energy Use Status] to access the Energy Use
Status screen.
Important: The following settings are required beforehand to display a graph.
• Energy Management Settings (via the Web Browser for Initial Settings)
• Measurement (via the Web Browser for Initial Settings)
Note: A separate license is required, depending on the selected date range, display range, and display item.
Note: Comparison data between the AE-200 and the AE-50/EW-50, as well as between different AE-50/EW-50 controllers, can
be displayed in a graph on the AE-200/AE-50's LCD, but cannot be displayed on this screen on the Web browser.
Note: In case the AE-200/AE-50/EW-50 malfunctions, it is recommended to periodically save the file in the CSV format by
clicking [Download] on this screen or by clicking [Output as CSV file] on the CSV output screen (see section 9-5).
Display range
Display target
Date to display the data
Display item
Download
Click to export the data in
the CSV format.
Item
Date range
Display range
WT07139X02
Select [Day], [Month], or [Year].
Note: When [Day] is selected, the data for each hour between 0:00 and 24:00 of the specified date
will appear in the graph.
When [Month] is selected, the data for each day between the 1st and 31st of the specified
month will appear in the graph.
When [Year] is selected, the data for each month between January and December of the
specified year will appear in the graph.
Note: All selected items in the [Display range], [Display target], [Date to display the data,
[Comparison target], [Comparison date], and [Display item] fields will be cleared when the
Date range is changed.
Note: Only the data for the period during which the AE-200/AE-50/EW-50 was powered on will
appear in the graph. The data for the period during which the AE-200/AE-50/EW-50 was
powered off will not appear in the graph.
Select [Block], [Group], or [Address] to display its data. (Clicking on this area shows a pulldown
menu.)
Description
31
Comparison target
Date range
Refresh screen
Click to show the graph
created based on the
specified criteria.
Comparison date
Graph region