8. CAPACITY TABLES
3. Power input of outdoor unit
<Cooling>
(1) Nominal power input of outdoor unit
(2) Calculation of the average indoor temperature power input coefficient
Average indoor temp. power input coefficient (
= 1.09 × 36/(36 + 36 + 1.03 × 36/(36 + 36
= 1.06
(3) No need to consider Coefficient of the partial load (CTi/CTo)
(4) Outdoor power input (PIo)
Maximum System Capacity (CTx = Total Outdoor unit Capacity (CTo , so use the following formula
PIo = Outdoor unit Cooling Nominal Power Input × Correction Coefficient of Indoor temperature
= 4.55 × 1.06
= 4.82 kW
MEES23K040
n
c
=
{c
×
(M
k
ave
k=1
n: Total number of the indoor units
k: Number of the indoor unit
c
: Outdoor unit power input coefficient of k indoor unit room temp.
k
M
: Number part of the k indoor unit model (e.g. P36
k
4.55 kW (Nominal)
1.09
1.03
n
/
M
k
k
k=1
-