1. SPECIFICATIONS
Outdoor Model
Indoor Model
Power source
Cooling capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
cooling
Outdoor
Heating capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
heating
*3 Outdoor
Indoor unit
Total capacity
connectable
Model/Quantity
Sound power level (measured in anechoic room) *4
Refrigerant
Liquid pipe
piping diameter
Gas pipe
Minimum Circuit Ampacity
Maximum Overcurrent Protection
FAN
Type x Quantity
Airflow rate
Control, Driving mechanism
Motor output
*5 External static press.
Compressor
Type x Quantity
Manufacture
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Fan motor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
Notes:
1.Cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230)
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices,
including the use of a backup source for heating.
4.Cooling mode/Heating mode
5.External static pressure option is available (0.12 in.WG, 0.24 in.WG, 0.32 in.WG/30 Pa, 60 Pa, 80 Pa).
* Due to continuing improvement, above specifications may be subject to change without notice.
MEES23K040
Non-Ducted
*1 BTU/h
kW
kW
A
BTU/h
kW
kW
A
W.B.
D.B.
*2 BTU/h
kW
kW
A
BTU/h
kW
kW
A
D.B.
W.B.
dB <A>
in. (mm)
in. (mm)
A
A
cfm
3
/min
m
L/s
kW
kW
kW
in.
mm
lbs (kg)
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
PUHY-P72YNU-A (-BS)
3-phase 3-wire 460 V ±10% 60 Hz
72,000
21.1
5.02
7.0
69,000
20.2
4.75
6.6
59~75°F (15~24°C)
23~126°F (-5~52°C)
80,000
23.4
5.42
7.5
76,000
22.3
4.89
6.8
59~81°F (15~27°C)
-13~60°F (-25~15.5°C)
50~130% of outdoor unit capacity
P04~P72/1~18
74.5/76.5
3/8 (9.52) Brazed
7/8 (22.2) Brazed
13
20
Propeller fan x 1
6,000
170
2,830
Inverter-control, Brushless DC motor
0.92
0 in.WG (0 Pa)
Inverter scroll hermetic compressor x 1
MITSUBISHI ELECTRIC
Inverter
3.8 x 1
-
MEL32
Pre-coated galvanized steel sheet (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
71-5/8 x 36-1/4 x 29-3/16
1,818 x 920 x 740
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-current protection
-
R410A x 14 lbs + 5 oz (6.5 kg)
LEV and HIC circuit
503 (228)
Salt-resistant cross fin & copper tube
Copper pipe, tube-in-tube structure
Auto-defrost mode (Reversed refrigerant cycle)
KL94T776
KE94G653
Installation Manual
Details refer to External Drw
joint: CMY-Y102SS/102LS-G2
Header: CMY-Y104/108/1010C-G
Y-Series
Ducted
4.54
6.3
5.13
7.1
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.