Toshiba MMY-MAP0806FT8P-E Installation Manual page 24

Air conditioner (multi type)
Hide thumbs Also See for MMY-MAP0806FT8P-E:
Table of Contents

Advertisement

Address setting procedure 2
1
Set a system address for each system using SW13 and 14 on the interface P.C. Board on the
header outdoor unit of each system.
(Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line)
or a custom side.
Interface P.C. Board on the header outdoor unit
SW06
SW07
SW09
1 2 3 4
1 2 3 4
1 2 3 4
SW11
SW12
SW13
1 2 3 4
1 2 3 4
1 2 3 4
Switch settings for a line (system) address on the interface P.C. Board on the outdoor unit
( : switch ON,
: switch OFF)
Line (system) address
1
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
45-EN
SW10
1 2 3 4
SW14
1 2 3 4
SW13
SW14
3
4
1
2
– 23 –
Line (system) address
26
27
28
" ": not used for system address setting (Do not change their positions.)
2
Be sure to disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals on all
the header outdoor units that will be connected to the central control. (Factory default:
disconnected)
3
Turn on indoor units rst, and then turn on outdoor units.
4
About 1 minute after turning the power on, con rm that the 7-segment display on the interface
3
4
P.C. Board of the header outdoor unit indicates
5
Press SW15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line's setting.)
6
The 7-segment display indicates
After the indication,
When the ashing stops and
complete.
7
Repeat steps
8
After completing address setting of all systems, turn off DIP switch 2 of SW30 on the interface
P.C. Boards of all the header outdoor units connected to the same central control, except the
unit that has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
SW13
1
2
3
4
2
U1
U2
S
U3 U4
TO
TO
SHIELD
CENTRAL
INDOOR UNIT
CONTROLLER
U. 1. L08 ( U. 1. ash )
Auto 1
Auto 2
Auto 3
starts ashing on the display.
U. 1. - - - ( U. 1. ash )
U. 1. - - - ( U. 1. light ) ,
remains lit on the display, the setting is
4
6
to
for other refrigerant lines.
SW14
1
2
3
4
U5 U6
S
TO
SHIELD
OUTDOOR UNIT
.
.
46-EN