Suction-Side Gas Pipe - Toshiba MMY-MAP0806FT8P-E Installation Manual

Air conditioner (multi type)
Hide thumbs Also See for MMY-MAP0806FT8P-E:
Table of Contents

Advertisement

• Anchor bolt positions are as shown below:
310 or
Continuous hole
more
A
(15 x 20 long hole)
Model type
MAP080*, MAP100*
MAP120*, MAP140*
MAP160*, MAP180*, MAP200*
2. When drawing out the refrigerant pipe from the
underside, set the height of the stand to 500 mm
or more.
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it ts under the whole clamping leg.
Correct
Install the vibration-proof
Anchor bolt
rubber so that the bent
part of the xing leg is
Vibration-proof rubber
grounded.
Incorrect
The bent part of
the xing leg is not
grounded.
11-EN
310 or
more
C*
A
A
A
B
B
*Only MAP160,
MAP180, MAP200
type has holes for
additional strength.
A
B
700
990
920
1210
1310
1600
1500
3. Do not use 4 stands on the corner to support the
outdoor unit.
Incorrect
Correct
Correct
Incorrect
Incorrect
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of
capacity from the one with the largest capacity. (A (Header unit)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1, 3 and 6)
• Be sure to use a T-shaped branch joint (RBM-BT14FE/RBM-BT24FE: separately purchased) to connect each
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe ows directly into
the header unit.)
• When attaching a Y-shaped branch unit for the outdoor unit connection piping kit, attach it level with the
ground (Be sure not to exceed ±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no
restriction for its angle.
(Unit : mm)
(Horizontal line)
C
A
(A arrow view)
B
• In case of using the Y-shaped branching joint for connecting between
outdoor units (Discharge gas joint and Suction gas joint), please keep
the straight part of at least 500 mm at the inlet.
Discharge side gas piping / Liquid piping
Figure 1
Correct
Header unit A
Main pipe
To indoor unit
Suction side gas piping
Figure 3
Correct
Header unit
A
Main pipe
To the indoor unit
– 6 –
B
At a level position
(Horizontal line)
Within ±15 degrees
(B arrow view)
Figure 2
Incorrect
Header unit A
Follower unit B
Follower unit C
Liquid joint
To indoor unit
Discharge gas joint
[Inverse connection of suction gas joint]
Figure 4
Incorrect
Follower unit
Follower unit
Header unit
B
C
A
Main pipe
Suction gas joint
To the indoor unit
C)
Do not connect
Within ±15
a branch unit
degrees
vertically.
Follower unit B
Follower unit C
Liquid joint
Main pipe
Discharge gas joint
Follower unit
Follower unit
B
C
EN
ID
ID
Suction gas joint
12-EN

Advertisement

Table of Contents
loading

Table of Contents