I/O Signal List; One Station Is Occupied (Cc-Link Ver.1) (C122=0) - Toshiba TOSVERT VF-S15 series Function Manual

Tosvert vf-s15 series cc-link option unit
Hide thumbs Also See for TOSVERT VF-S15 series:
Table of Contents

Advertisement

5.5.

I/O signal list

5.5.1. One station is occupied (CC-Link Ver.1) (c122=0)

This option occupies one station area of the buffer memory of the PLC.
In the case of c122 = 0, there are remote I/O (RX, RY both 32 bits) and the remote register
(RWw, RWr both 4 word) in the communication data for one station area.
Remote I/O (Default value = 0)
Inverter (Slave) → PLC (Master)
Device No.
RXn0
Forward running
RXn1
Reverse running
RXn2
Output terminal 1 (RY-RC)
RXn3
Output terminal 2 (OUT)
RXn4
Output terminal 3 (FL)
RXn5
Failure FL
RXn6
PI control OFF
Acceleration/deceleration
RXn7
pattern selection (1 or 2)
RXn8
Emergency stop
RXn9
Coast stop (ST = OFF)
RXnA
Alarm
RXnB
Reserved*
RXnC
Monitoring
Frequency setting completion
RXnD
(RAM)
RXnE
Reserved*
Instruction code execution
RXnF
completion
RX(n+1)0
to
Reserved*
RX(n+1)9
RX(n+1)A
Error status flag
RX(n+1)B
Remote station ready
RX(n+1)C
to
Reserved*
RX(n+1)F
"n" is depend on the station number.
* The bit described "
Reserved
** Set OFF ("0") to reserved bit.
Remote register (Default value = 0)
RWr
Address
RWr n
Monitor value 1
Monitor value 2
RWr n+1
(output frequency)
RWr n+2
Reply code
RWr n+3
Read data
"n" is depend on the station number.
Signal
" is unstable. Don't use the "
Inverter → PLC
Signal
PLC (Master) → Inverter (Slave)
Device No.
RYn0
Forward rotation command
RYn1
Reverse rotation command
RYn2
Input terminal 3 (S1)
RYn3
Input terminal 4 (S2)
RYn4
Input terminal 5 (S3)
RYn5
Input terminal 6 (S4)
RYn6
Input terminal 7 (PIOFF)
RYn7
Input terminal 8 (AD1)
RYn8
Input terminal 9 (ESTP)
Intercept output to inverter
RYn9
(Coast stop)
RYnA
Frequency priority CC-Link
RYnB
Command priority CC-Link
RYnC
Monitor command
Frequency setting command
RYnD
(RAM)
RYnE
Reserved**
RYnF
Instruction code execution request
RY(n+1)0
to
Reserved**
RY(n+1)9
Error reset request flag
RY(n+1)A
(A reset request is during switched
ON)
RY(n+1)B
Reserved**
RY(n+1)C
to
Reserved**
RY(n+1)F
" bit for the judgment.
Reserved
RWw
Address
RWw n
Monitor code (1 and 2)
RWw n+1
Set frequency
RWw n+2
Instruction code
RWw n+3
Write data
- 17 -
E658130
Signal
PLC → Inverter
Signal