6.2.

Program example for setting the operation mode

Example 2 shows
The operation mode of station 1 inverter can be changed to network operation.
Operation mode writing code number: 2003H (hexadecimal)
Network operation set data: 0004H (hexadecimal)
The reply code at the time of instruction code execution is set to D2.
X0
X0F
M0
X20
M300
M301
X100F
M302
X100F
Example
a ladder logic to
SW80.0
X1
[ MOV H2003 W102]
[ MOV H0004 W103]
write data in the inverter.
( M0)
Check the ready of the station 1
[ PLS M300]
[ SET M301]
Write operation mode write code
(2003H) to RWw2 and set data
(0004H) to RWw3.
Turn
execution
[ SET Y100F]
[ RST M301]
[ SET M302]
Read reply code (RWr2) to D2 when the
Instruction code execution completion
flag
[ MOV W2 D2]
Turn
[ RST Y100F]
execution
[ RST M302]
[ END]
- 39 -
E658130
on
the
instruction
off
the
instruction
code
code