Toshiba G8000 SERIES Installation And Operation Manual page 19

480/208 v 100/150 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

Item
environment standard
Installation location Indoors
minimum operating temperature: 32
Maximum operating temperature: 86
battery system).
Ambient
maximum operating temperature: 90
Temperature
system).
maximum operating temperature: 104
Average 24-hour operating temperature: 86
(5
The relative humidity must be between 30 and 90% and without condensation
relative Humidity
due to temperature changes.
These specifications are for altitudes up to 3240 ft. (1000 m) above sea level.
Altitude
Consult with the factory to determine the derating factor for installations above
3240 ft. (1000 m).
Installation environment must not have vibration frequencies 10 Hz - 20 Hz
The acceleration due to vibrations less than 10 Hz must not exceed 0.5 G
Vibration and
mechanical Shock
The acceleration due to vibrations 20 Hz - 50 Hz must not exceed 0.5 G
The total amplitude due to vibrations 50 Hz - 100 Hz must not exceed 0.1 mm
Dust must not exceed normal atmospheric levels and must not include conductive
Dust
particles, silicone or oils.
No flammable and/or explosive gas.
Hydrogen sulfide (H
Sulfurous acid gas (So
Chlorine gas (Cl
Ammonia gas (nH
Flammable Gas
nitrous acid gas (no
nitrous oxides (nox)
ozone (o
Hydrochloric acid mist (HCl)
Installation Precautions
1) Install the unit in a stable, level and upright position that is free of excessive
vibration.
2) Install the unit where the ambient temperature is within the specified range.
3) Do noT install the UpS in areas that are subject to high humidity.
4) Do noT install the UpS in areas that allow exposure to direct sunlight.
5) Do noT install the UpS in areas that allow exposure to high levels of airborne dust,
metal particles, or flammable gases.
6) DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper
earth ground will reduce the effects of electrical noise and will reduce the potential for
G8000 Series with Isolated output Installation and operation manual
TABLE 5.1 - UPS INSTALLATION ENVIRONMENT STANDARDS
35 °C) at 0.8 pF.
S)
2
)
2
)
2
)
3
)
2
)
3
°F
(0 °C).
°F
(30 °C) at 1.0 pF (UpS with/without
°F
(32 °C) at 0.8 pF (UpS with battery
°F
(40 °C) at 0.8 pF (UpS only).
°F
(30 °C) at 1.0 pF and 41
less than or equal to 0.0001 ppm
less than or equal to 0.05 ppm
less than or equal to 0.002 ppm
less than or equal to 0.1 ppm
less than or equal to 0.02 ppm
less than or equal to 0.02 ppm
less than or equal to 0.002 ppm
less than or equal to 0.1 mg/m3
– 95 °F
11