Toshiba G8000 SERIES Installation And Operation Manual page 53

480/208 v 100/150 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

MEASUREMENT SCREENS
O/P CURRENT (PEAK)
U
50[%]
V
50[%]
W
50[%]
AC INPUT
AC I/P-V 480[V]
FREQ. 60.0[Hz]
BYPASS INPUT
BYP I/P-V 480[V]
FREQ.
60.0[Hz]
BATTERY
BACK-UP RATING 10[MIN]
DISCHARGING
DC INPUT
DC-V
632[V]
BATT-V 400[V]
BATT- I
MODE COUNT
UPS
BATTERY
CLOCK
TIME 03-24-06 13:58
G8000 Series with Isolated output Installation and operation manual
TABLE 13.2 - CONTINUED
Shows the peak output current peak (%) for each phase.
Shows the AC Input Voltage (line-to-line) and frequency.
Shows the bypass Input Voltage (line-to-line voltage) and
frequency. .
Shows the remaining battery backup time with rated load
and cumulative discharged time.
15[MIN]
Shows the internal DC bus voltage, battery voltage and
battery current.
The battery current value displayed is negative during
recharge and positive during discharge.
0[A]
Shows the cumulative UpS operation time, the
cumulative battery backup time and the number of battery
35[H]
backup operations.
56[MIN]
32[TIM]
The current time is displayed if there are no faults
recorded, or after the reset button is pressed.
Date is displayed in the mm-ddyyy format. The unit does
not calculate daylight savings time.
Time is displayed in the 24-hour format (e.g. 1:58 p.m. =
1358 Hrs.)
peak value of output current
rmS value for rated current x 1.41
x 100 [%]