ANCB LEDs Description and Operation,
ADHA and ADHB -
IMPORTANT
LOCKA and LOCKB -
E1A / E1B OK ER -
50
Troubleshooting
During normal operation the Green LED for ADHA or ADHB will blink to
indicate either receive or transmit activity on the ANG_EN channel. If a
message retry is sent the Yellow LED will blink.
The ADHA and ADHB LEDs are status indicators. During reset all of the
LED's will blink for ½ second while the board goes through self-test. If an
error is detected during the self-test period the Red FAULT LED will re-
main on and the Yellow WARN LED will blink the detected error code.
Only the Channel A ADHA LED's will display FAULT codes. Use the fol-
lowing table to determine the error condition.
NUMBER
of Blinks
1
RAM FAILURE
2
FLASH FAILURE
3
ETHERNET FAILURE
4
DataNET FAILURE
5
OTHER HARDWARE FAILURE
6
DUPLICATE IP
7
CROSS LINK FAILURE
8
WRONG LOOP
9
INVALID JUMPER
CONFIGURATION
10
DUPLICATE UNIT NUMBER
FAULT errors can only be cleared with a board reset.
If either of the LOCKA or LOCKB LED's is on, the board must be reset.
This is indication that the board left the 455Khz Line Contention signal on
for more than +/- 2.3 seconds.
These LEDs are used to indicate ANG_EN status and activity. The
Green LED will blink whenever a message is received or transmitted on
the respective channel. The Red LED will blink if an error has occurred
on the channel.
Continued
Type of Error
Corrective Action
Replace Board
Reload Firmware or Replace
Board
Replace Board
Replace Board
Replace Board
Change Board IP address
Check Cross Link Cable
Change Loop Number
Check J10 and J11 Connec-
tions
Change Unit Number
2000590-001