Miscellaneous
Settings
"B" Function
Func.
Name
Code
B034 Run/power-on warning
time
B035 Rotational direction
restriction
B036 Reduced voltage start
selection
"B" Function
Func.
Name
Code
B037 Function code display
restriction
The miscellaneous settings include scaling factors, initialization modes, and others. This
section covers some of the most important settings you may need to configure.
Description
Range is 0 to 65,530 hours
Three option codes:
00 Enable for both dir.
01 Enable for forward only
02 Enable for reverse only
Seven option codes:
00 Short
01, 02, 03, 04, 05 (middle)
06 Long
Function Code Display Restriction – The inverter has the (optional) capability to suppress the
display and editing of certain parameters. Use B037 to select the display options. The purpose
of this feature is to hide particular secondary parameters that become unused or not applicable
based on more fundamental parameter settings. For example, setting A001 = 01 configures the
inverter to get its frequency command from the front keypad potentiometer. In this case, the
inverter will not use the analog inputs nor their adjustment parameters for an external frequency
command.
Description
Three option codes:
00 Display all
01 Display only utilized
functions (see table
below)
02 Display user-selected
functions only (con-
figure with U01 to U12)
For example, you can set B037=01 to have the inverter suppress the displaying of all analog
input parameters when A001=01, as shown in the first row of the following table.
Function
Data
Code
A001
01
A002
01, 03, 04,
05
A019
00
C001 – C008 02, 03, 04,
05
Defaults
Run
Mode
Edit
–FE
–FU
Lo Hi
(EU)
(US)
✘ ✔
0.
0.
✘ ✘
00
00
✘ ✔
06
06
Defaults
Run
Mode
Edit
–FE
–FU
Lo Hi
(EU)
(US)
✘ ✔
00
00
Resulting Non-displayed
Functions (when B37 = 01)
A005, A006, A011 – A016,
A101 – A114, C081 – C083,
C121 – C123
B087
A028 – A035
SJ300 Inverter
SRW Display
Units
–FR
(JP)
0.
hrs.
>b034 TIME
WARN
00
>b035 LIMIT
F/R
06
>b036 RVS
ADJUST
SRW Display
Units
–FR
(JP)
00
>b037 DISP
Mode
ALL
Notes
[O], [OI], [O2] terminal
functions
Stop key function
Multi-speed function
3–37
00000
FREE
06