Sj300-007Hfu/E; Sj300-015Hfu/E; Sj300-022Hfu/E; Sj300-040Hfu/E - Hitachi SJ300 Series Instruction Manual

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

Terminal dimensions and torque specs, continued...
Motor
Output
Input
Inverter Models
Voltage
HP
kW
1
0.75

SJ300-007HFU/E

2
1.5

SJ300-015HFU/E

3
2.2

SJ300-022HFU/E

5
4.0

SJ300-040HFU/E

7.5
5.5

SJ300-055HFU/E

10
7.5
SJ300-075HFU/E
15
11
SJ300-110HFU/E
20
15
SJ300-150HFU/E
25
18.5
SJ300-185HFU/E
400V
30
22
SJ300-220HFU/E
40
30
SJ300-300HFU/E
50
37
SJ300-370HFU/E
60
45
SJ300-450HFU/E
75
55
SJ300-550HFU/E
100
75
SJ300-750HFU/E
125
90
SJ300-900HFU/E
150
110
SJ300-110HFU/E
175
132
SJ300-1320HFE
200
150
SJ300-1500HFU
Note 1: The recommended ring lug connector listing consists of wire size – screw size
format. The wire sizes are in AWG or mm
for the ring lug centers are: #10, #12, 1/4", 5/16", and 1/2". For metric wire sizes,
bolt sizes for the ring lug centers are: 6 = 6M, 8 = 8M, 10 = 10M.
400V
Screw size
of terminal
M4
M4
M4
M4
M5
M5
M6
M6
M6
M6
M6
M6
M8
M8
M8
M10
M10
M10
M10
SJ300 Inverter
Ring lug connector *1
2
(AWG-bolt)
(mm
–bolt)
20–#10
1.25–4
14–#10
2–4
14–#10
2–4
14–#10
2–4
14–#12
2–5
10–#12
3.5–5
8–1/4
5.5–6
6–1/4
8–6
4–1/4
14–6
4–1/4
14–6
2–1/4
22–6
1–1/4
38–6
1/0–5/16
38–8
2–5/16
60–8
1–1/2
100–10
1/0–1/2
100–10
1/0–1/2
150–10
2/0–1/2
80x2–10
2/0–1/2
80x2–10
2
format. For AWG wire sizes, bolt sizes
2–17
Torque
ft-lbs
(N-m)
1.1
1.5
1.1
1.5
1.1
1.5
1.1
1.5
1.8
2.5
1.8
2.5
3.6
4.9
3.6
4.9
3.6
4.9
3.6
4.9
3.6
4.9
3.6
4.9
6.5
8.8
6.5
8.8
6.5
8.8
10.1
13.7
10.1
13.7
10.1
13.7
10.1
13.7

Advertisement

Table of Contents
loading

Table of Contents