Application Example: Juice Batch Tank With Sanitary Horn Antenna - Siemens SITRANS LR 300 Instruction Manual

Iq radar 300
Hide thumbs Also See for SITRANS LR 300:
Table of Contents

Advertisement

Application Example: Juice Batch Tank with Sanitary
Horn Antenna
Notes:
• The minimum distance from the flange face to the target is limited by near-blanking
P800.
• Only set P837 if the product is at least 2m (78") away from the flange face. If it is
closer, leave P837 at 1 until the level drops and the distance increases beyond
2m (78").
• Choose First only (P820 = 12) if the SITRANS LR 300 is in the center. Otherwise,
keep it at 8 (bLF).
• Sanitary Antenna Options: The one-piece antenna/process seal provides an
excellent mounting method, even on non-sanitary installations.
Mixer
P006
P007
Parameter
P999
P001
P002
P003
P004
P005
P006
P007
P070
P071
P820
P830
P837/838
(Note above)
Run: To start normal operation, press the PROGRAM key
7ML19985CL02
Existing 4"
tri-clamp
connection
Mixer
Enter
----
master reset
1
mode of measurement
1
material
2
measurement response
240
antenna
1
units
5
empty distance
4.5
span
2
Fail-Safe timer
1
Fail-Safe
12
algorithm
7
TVT type
2 & 1
Auto False Echo Suppression
SITRANS LR 300 – INSTRUCTION MANUAL
4" Sanitary Horn
This application is to obtain a level
measurement and corresponding
4-20 mA output proportional to the
juice level on a batch process tank.
The bottom of the horn is 5m from
the tank bottom. The empty level is
0m (bottom) and the full level (span)
is 4.5m from the bottom. The
maximum rate of filling or emptying
is about 0.5m/min.
In the event of a loss of echo, the
SITRANS LR 300 is to go into Fail-
Safe Hi after 2 minutes.
= level
= liquid
= 1m/min.
= factory
= meters
= 5m
= 4.5m
= 2 minutes
= Hi
= First Echo
= factory
.
Page 51